TRILOGY....... 45 ÷ 210 kW

MAIN FEATURES
Reversible heat pump and multifunction chiller.
3 versions available 15 models available, for a wide selection opportunity..
Average step of 25kW.
EER up to 3,24.
COP up to 3,73.
ESEER up to 4,53.
Scroll compressors.
Single refrigerant circuit.
R410A refrigerant charge.
Plate type heat exchanger.
EC axial fans.
Single air circuit.
Electronic expansion valves.
Suitable for outdoor installation.
 
IDEA® DEFROSTING SYSTEM
“Patented” defrosting system with dynamic reading of working parameters. Thanks to proprietary software it senses the real
presence of brine on the coil starting defrosting cycles only in that situation. This brings a remarkable energy saving (more than 20-
30% on the average) and a higher working continuity compared with
traditional systems.

WORKING LIMITS IN COOLING MODE
Evaporator chilled water outlet temperature: -10÷15°C Ambient temperature: -12÷18°C

WORKING LIMITS IN HEATING MODE
Condenser hot water outlet temperature: 30÷60°C Ambient temperature: -10÷35°C
 

MAIN BENEFITS
Defrosting dynamics control system IDEA®.
Availability of pumping groups.
Availability of kit for the reduction of the noise.
EC fans for a higher efficiency.
Easily of maintenance.

ELECTRONIC EXPANSION VALVE
The electronic expansion valves are synonymous of an higher energy efficiency and stability of the system.
 

 
WORKING LOGIC

TRILOGY BI
The production of sanitary hot water is made through partial or total heat reclaim systems and it matches the normal production of chilled or hot  water according to the following schemes. In working condition 2 the system produces simultaneously chilled water and domestic hot water. In working condition no. 4 (simultaneous request of hot water for heating and domestic hot water) the system gives priority to the domestic hot water production. Only when the domestic hot water request is satisfied, the system will start producing hot water for heating.

AIR/GAS HEAT EXCHANGER
Heat exchanger coil with internally corrugated copper tubes and high efficiency aluminium fins, specifically developed to provide high heat transfer and lower pressure drops. The combination of two factors, special tubes and fins, allow to optimally combine the following aspects:
Maximum capacity relative to the size of the exchanger.
Minimum charge of refrigerant.
Reduction of the air flow required for the heat exchange.
Particular circulation on refrigerant side, in order to optimize performance in heat pump mode.
Ambient temperature sensor
Frame in galvanized steel.
 

FANS SECTION
Axial fans with sickle-shaped blades, fan guard and optimized for low noise levels.
Brushless type synchronous EC motors with integrated electronic commutated system and continuous variation of the rotation speed. The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the 0÷10V proportional signal coming from the microprocessor control system.
IP54 enclosure class.
 

 

 

 

 

 

 

 

 

TRILOGI BI COMPONENTS
FRAMEWORK
Base, self supporting frame and panelling in steel plate with protective surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with epoxy powders.
Technical compartment housing compressors and heat exchangers. Technical compartment and panels insulated with polyurethane for sound proofing.
Colour: RAL 9002

COMPRESSORS
Orbiting spiral (SCROLL) hermetic compressors with spiral profile optimized for R410A refrigerant.
ON / OFF capacity control (0 / 100% each compressor).
2-pole 3-phase electric motor with direct on line starting.
Phase sequence electronic relay.
Crankcase heater.
Electric motor thermal protection via internal winding temperature sensors.
Rubber supports.

PLANT SIDE HEAT EXCHANGER
Copper brazed plate type with cover plates, plates and connections in AISI 316 stainless steel:
Anticondensate insulation made of polyurethane.
Temperature sensors on water inlet and outlet.
Differential water pressure switch for water flow control.
Antifreeze heater.
 
REFRIGERANT CIRCUIT
Reversing valve for refrigeration cycle inversion.
Electronic expansion valves.
One valve on plant side heat exchanger
One valve on source side heat exchanger (finned coil)
The electronic expansion valve allows high performance and system efficiency thanks to a timely and accurate response to changes in temperature and pressure. The electronic expansion valve exclude the installation of the electromagnetic valve on liquid line.
Sight glass.
Liquid receiver with service valve and safety valve.
Filter dryer on liquid line.
Service valves on suction line and gas discharge.
Non-return valve
Solenoid valve on liquid line
Safety valve on low pressure side.
Safety valve on high pressure side.
Pressure transducers with indication, control and protection functions, on low and high refrigerant pressure.
High pressure safety switch with manual reset.
Oil drainage and oil recovery systems.
Liquid separator on suction line.
IDEA® defrosting system.
RC Group patented defrosting system based on a dynamic reading of the evaporating parameters.
Through sensors the microprocessor realize the real ice presence on the gas/air heat exchanger and activates the defrosting cycle only when necessary, with consequent energy saving.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R410A refrigerant charge.

ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation, complete with:
Main switch with door lock safety.
Magnetothermic switch or fuses for each compressor.
Magnetothermic switches for fans or water pumps (if scheduled).
Contactors for each load (fans excluded).
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls:
Working mode selector Summer – Winter – Remote
Enabling selector On – Off - Remote
Power supply: 400/3/50+N.
 
Heat Pumps & Multifunction

CONTROL SYSTEM
MP.COM microprocessor system with graphic display for control and monitor of operating and alarms status. The system includes:
Voltage free contact for remote general alarm.
Main components hour-meter.
Nonvolatile “Flash” memory for data storage.
Menu with protection password.
LAN connection.
 

HYDRAULIC CONNECTIONS OF HEAT EXCHANGERS
The threaded hydraulic connections are available up to a diameter of 3 “ included, and correspond to ISO 7/1 - R.
The hydraulic connections with flange (FL) are supplied as standard with counter flange.
The hydraulic connections with grooved end (Victaulic) are supplied as standard with Victaulic joint and adapter pipe.