NEMO A 2013...... 5,4 ÷ 26,0 kW

MAIN FEATURES
Motoevaporating unit.
13 models available, for a wide selection opportunity.
Average step of 2,5kW.
EER up to 3,02.
Scroll compressor.
R410A Refrigerant charge.
Single refrigerant circuit.
Plate type heat exchanger.
Suitable for indoor installation.

MAIN BENEFITS
Availability of partial heat recovery system.
Availability of kit for the reduction of the noise.
Availability of remote condensers with axial fans (TEAM MATE series) and with plug fan (TEAM MATE PF series).
Easily of maintenance.
Eurovent Certification.
 
INDOOR INSTALLATION
The machines are designed for indoor installation.

REMOTE CONDENSER
The units are designed to be matched with remote condensers with axial fans (TEAM MATE series) or plug-fan (TEAM MATE PF series).

COMPLETENESS OF EQUIPMENT AND OPTIONAL
The units are standardly equipped with 3-speed water pump.
On request is possible to install the system for the domestic hot water production and a chilled water tank.

WORKING LIMITS IN COOLING MODE
Evaporator chilled water outlet temperature: -12÷20°C Ambient temperature: -10÷45°C
 

 
MAIN COMPONENTS
FRAMEWORK
Base, self supporting frame and paneling in steel plate with protective surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with epoxy powders.
Colour: RAL 9002
Insulation of the internal framework.
 
TO BE MATCHED WITH REMOTE CONDENSER
The units are designed to be matched with remote condensers with axial fans (TEAM MATE series) or plug-fan (TEAM MATE PF series).
 

COMPRESSOR
Orbiting spiral (SCROLL) hermetic compressors with spiral profile optimized for R410A refrigerant.
ON / OFF capacity control (0 / 100%).
Crankcase heater.
Electric motor thermal protection via internal winding temperature sensors.
Rubber supports.
Electric motor:
Version M: single-phase electric motor with direct on line starting.
Version T: 2-pole 3-phase electric motor with direct on line starting.
Phase sequence electronic relay.

EVAPORATOR
Copper brazed plate type with cover plates, plates and connections in AISI 316 stainless steel.
Anticondensate insulation made of polyurethane.
Temperature sensors on water inlet and outlet.
Differential water pressure switch for water flow control.
3-speed circulation pump.

REFRIGERANT CIRCUIT
Thermostatic expansion valve.
Service valves on liquid line and gas discharge.
Pressure transducers with indication, control and protection functions, on low and high refrigerant pressure.
0÷10V proportional signal to manage the condensing control system of the remote air cooled condenser.
High pressure safety switch with manual reset.
Refrigerant circuit with copper tubing with anticondensate insulation of the suction line.
Plastic capillary hoses for pressure sensors connection.
R410A refrigerant charge.

ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for indoor installation complete with:
Main switch.
Magnetothermic switch or fuses for compressor.
Contactor for compressor.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply:
M: 230/3/50
T: 400/3/50+N

CONTROL SYSTEM
Microprocessor control. The system includes:
Display for the visualization of the alarm codes, set values and temperature values.
Dynamic set point.
Compressor running hour meter.
Contact for general alarm remotization.
“Low Temperature” set for operation with ambient air temperature up to
-10°C.

HYDRAULIC CONNECTIONS OF HEAT EXCHANGERS
The heat exchangers’ threaded hydraulic connections correspond to ISO 228/1 – G M