MANTA.....A ....HP ..... 23 ÷ 365 kW

MAIN FEATURES
Split-system liquid chiller.
28 models available, for a wide selection opportunity..
Average step of 25kW.
EER up to
COP up to
ESEER up to
Scroll compressors.
R410A Refrigerant charge.
Single, double refrigerant circuit.
Plate type heat exchangers.
Suitable for indoor installation.
Split-system.

MAIN BENEFITS
Units equipped with two compressors for refrigerant circuit to reach a high efficiency.
Units with single and double refrigerant circuits.
Availability of remote air/gas heat exchanger with axial fans (TEAM MATE HP series) and with plug fan (TEAM MATE HP PF series).
Availability of partial and total heat recovery system.
Easily of maintenance.

REMOTE EXCHANGER
The units are designed to be matched with remote exchanger with axial fans (TEAM MATE HP series) or plug-fan (TEAM MATE HP PF series).

REDUCED NOISE EMISSION
The machines are characterized by a low sound level guaranteed by the containing structure.

DOMESTIC HOT WATER
On request is possible to install the system for the domestic hot water production.

WORKING LIMITS IN COOLING MODE
Evaporator chilled water outlet temperature: -12÷20°C Ambient temperature: -10÷45°C

WORKING LIMITS IN HEATING MODE
Condenser hot water outlet temperature: 28÷58°C Ambient temperature: -12÷30°C

INDOOR INSTALLATION
The machines are designed for indoor installation.

 

MAIN COMPONENTS
FRAMEWORK
Base, self supporting frame and paneling in steel plate with protective surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with epoxy powders.
Colour: RAL 9002

COMPRESSORS
Orbiting spiral (SCROLL) hermetic compressors with spiral profile optimized for R410A refrigerant.
ON / OFF capacity control (0 / 100% each compressor).
2-pole 3-phase electric motor with direct on line starting.
Phase sequence electronic relay.
Crankcase heater.
Electric motor thermal protection via internal winding temperature sensors.
Rubber supports.

PLANT SIDE HEAT EXCHANGER
Copper brazed plate type with cover plates, plates and connections in AISI 316 stainless steel:
With single refrigerant circuit for S version machines.
With double refrigerant circuit for D version machines.
Anticondensate insulation made of polyurethane.
Temperature sensors on water inlet and outlet.
Differential water pressure switch for water flow control.

REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Reversing valve for refrigeration cycle inversion.
Electronic expansion valve. The valve allows high performance and system efficiency thanks to a timely and accurate response to changes in temperature and pressure. The expansion valve is equipped with energy reserve to allow the closure of the valve in the event of lack of power supply.
Sight glass.
Filter dryer on liquid line.
Service valves on liquid line and gas discharge.
Non-return valve.
Safety valves on high and low pressure side.
Pressure transducers with indication, control and protection functions, on low and high refrigerant pressure.
High pressure safety switch with manual reset.
Liquid receiver with accessories.
Oil drainage and oil recovery systems.
IDEA® defrosting system.
RC Group patented defrosting system based on a dynamic reading of the evaporating parameters.
Through sensors the microprocessor realize the real ice presence on the gas/air heat exchanger and activates the defrosting cycle only when necessary, with consequent energy saving.
Valves on gas delivery and liquid return for coupling to remote air cooled
condenser.
0÷10V proportional signal to manage the condensing/evaporating control system of the remote air cooled condenser.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R410A refrigerant charge.

ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for indoor installation complete with:
Main switch with door lock safety.
Magnetothermic switch or fuses for each compressor.
Contactors for each load.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Summer / Winter working mode selector.
Ambient temperature sensor.
Power supply 400/3/50.

CONTROL SYSTEM
MP.COM microprocessor system with graphic display for control and monitor of operating and alarms status. The system includes:
Voltage free contact for remote general alarm.
Main components hour-meter.
Clock card for alarms date and time displaying and storing.
Nonvolatile “Flash” memory for data storage.
Menu with protection password.
LAN connection.

HYDRAULIC CONNECTIONS OF HEAT EXCHANGERS
The heat exchangers’ threaded hydraulic connections are available up to a diameter of 3 “ included, and correspond to ISO 228/1 – G M.
The pipes’ threaded hydraulic connections are available up to a diameter of 3 “ included, and correspond to ISO 7/1 – R.
The hydraulic connections with flange (FL) are not supplied with counter
flange.
The hydraulic connections with grooved end are not supplied with flexible joint (optional accessory).

 

 

TO BE MATCHED WITH REMOTE AIR/GAS HEAT EXCHANGERS
The units are designed to be matched with remote air/gas heat exchangers with axial fans (TEAM MATE HP) or plug-fans (TEAM MATE HP PF) series.